Airflow / CFM & Static Pressure Calculator

Find airflow (CFM) from heat, velocity, or velocity pressure, verify delivered capacity with the 1.08 sensible formula, and check total external static pressure against field targets.

Use Calculator in App

What is Airflow & Static Pressure?

Airflow is the volume of air a system moves, measured in cubic feet per minute (CFM). Proper airflow is critical: too little starves the coil (frozen evaporator, poor dehumidification), while too much hurts latent removal and comfort. The industry rule of thumb is roughly 400 CFM per ton of cooling (typically 350–450 CFM/ton depending on climate and equipment).

Total external static pressure (TESP) is the resistance the blower works against, measured in inches of water column (iwc) with a manometer at the supply and return plenums. Most residential systems target 0.50 iwc or less; readings above 0.80 iwc signal restricted ducts, a dirty filter or coil, or undersized returns.

These calculations are estimates for reference. Always verify against the equipment nameplate, the blower performance table, and manufacturer specifications before making a diagnosis.

Target Airflow by Cooling Tonnage (~400 CFM/ton)

Typical required airflow for residential cooling systems at 350, 400, and 450 CFM per ton:

TonsNominal BTU/hr350 CFM/ton400 CFM/ton450 CFM/ton
1.518,000525 CFM600 CFM675 CFM
224,000700 CFM800 CFM900 CFM
2.530,000875 CFM1,000 CFM1,125 CFM
336,0001,050 CFM1,200 CFM1,350 CFM
3.542,0001,225 CFM1,400 CFM1,575 CFM
448,0001,400 CFM1,600 CFM1,800 CFM
560,0001,750 CFM2,000 CFM2,250 CFM

Total External Static Pressure (TESP) Guide

Interpreting a total external static pressure reading (measured in inches of water column):

TESP (iwc)StatusTypical CauseAction
≤ 0.50GoodCorrectly sized ducts, clean filterAirflow within spec
0.51 – 0.80ElevatedDirty filter, mild duct restrictionInspect filter/coil, monitor
0.81 – 1.00HighUndersized returns, dirty coil, closed dampersCorrect restriction — airflow reduced
> 1.00CriticalSevere blockage or crushed/collapsed ductFind and clear before running

Key Airflow Formulas

CFM from Heat

CFM = BTU / (1.08 × ΔT). Rearranged sensible-heat formula; ΔT is the return-minus-supply temperature split across the coil.

CFM from Velocity

CFM = Velocity (FPM) × Duct Area (ft²). Measure velocity with an anemometer; use ft², not square inches.

Velocity from Velocity Pressure

V = 4005 × √VP. Convert a pitot-tube velocity pressure (iwc) into air velocity in FPM.

Static Pressure Target

Total external static pressure should be ≤ 0.50 iwc; above 0.80 iwc indicates a restriction that is choking airflow.

Airflow Calculation Example

Problem:

A 3-ton system is delivering about 27,000 BTU/hr of sensible cooling. The tech measures a 20°F temperature split (ΔT) across the coil and a total external static pressure of 0.45 iwc. Find the airflow and check it against the 400 CFM/ton rule.

Solution:

CFM from heat: 27,000 / (1.08 × 20) = 1,250 CFM

Target airflow (400 CFM/ton): 3 × 400 = 1,200 CFM → 1,250 CFM is right on target

Velocity cross-check: a 20" × 10" plenum = 1.39 ft²; pitot VP of 0.05 iwc → V = 4005 × √0.05 ≈ 896 FPM; CFM = 896 × 1.39 ≈ 1,245 CFM

Static pressure: 0.45 iwc ≤ 0.50 iwc → healthy, no restriction

Result: ~1,250 CFM (≈417 CFM/ton) with 0.45 iwc TESP — airflow and static pressure both within spec

Instant Airflow & Static Pressure with Ventora

Enter heat and ΔT, duct velocity, or velocity pressure — get CFM instantly, plus the 400 CFM/ton check and static pressure targets built in. Free 7-day trial, then $19.99/month. Cancel anytime.

Download Free on App Store

Get All Calculators in One App

Download Ventora for instant access to all HVAC calculators, AI assistant, HVAC code reference, and more. Free to try.

Download on App Store