Duct Sizing Calculator
Size supply and return ductwork instantly. Enter target CFM and friction rate to get the right round diameter and equivalent rectangular dimensions, with velocity checked against ACCA Manual D targets.
Use Calculator in AppWhat is Duct Sizing?
Duct sizing determines the round diameter or rectangular dimensions needed to deliver a target airflow (CFM) at an acceptable friction rate and air velocity. Proper sizing keeps total external static pressure low, delivers full airflow to every room, and holds noise down.
Undersized ducts choke airflow, drive up static pressure, and cause comfort and efficiency problems. Oversized ducts waste material and can drop velocity so low that air stops throwing across the room. The goal is a diameter that lands airflow squarely inside the velocity targets below.
Velocity & Friction Rate Targets
Residential duct design keeps air velocity and friction rate inside proven ranges. Aim for these targets when selecting a size:
Target range for supply trunks and branches
Lower velocity keeps returns quiet
Typical residential design friction rate
Friction Rate = (Available Static Pressure / Total Equivalent Length) × 100 (iwc per 100 ft)
Round Duct Area = π × (D / 2)² (sq. in.)
Velocity = (CFM × 144) / Area (FPM, area in sq. in.)
Equivalent Round De = 1.3 × (a × b)0.625 / (a + b)0.25 (inches)
Round Duct Airflow Capacity (CFM by Velocity)
| Round Diameter | Area (sq. in.) | CFM @ 700 FPM | CFM @ 800 FPM | CFM @ 900 FPM |
|---|---|---|---|---|
| 6" | 28.3 | 137 | 157 | 177 |
| 7" | 38.5 | 187 | 214 | 241 |
| 8" | 50.3 | 244 | 279 | 314 |
| 9" | 63.6 | 309 | 353 | 398 |
| 10" | 78.5 | 382 | 436 | 491 |
| 12" | 113.1 | 550 | 628 | 707 |
| 14" | 153.9 | 748 | 855 | 962 |
| 16" | 201.1 | 977 | 1117 | 1257 |
Equivalent Round for Rectangular Ducts (De)
| Rectangular Size | Equiv. Round | Rectangular Size | Equiv. Round |
|---|---|---|---|
| 8" × 6" | 7.6" | 12" × 10" | 12.0" |
| 10" × 6" | 8.4" | 14" × 10" | 12.9" |
| 12" × 6" | 9.1" | 16" × 10" | 13.7" |
| 10" × 8" | 9.8" | 14" × 12" | 14.2" |
| 12" × 8" | 10.7" | 18" × 12" | 16.0" |
| 14" × 8" | 11.5" | 20" × 14" | 18.2" |
Duct Sizing Example
Problem:
A supply trunk must carry 800 CFM. There is 0.10 iwc of available static pressure over a total equivalent length of 100 ft. What round duct works, and what rectangular size is equivalent?
Solution:
Friction rate: (0.10 / 100) × 100 = 0.10 iwc per 100 ft
Required area at 800 FPM supply: 800 × 144 / 800 = 144 sq. in.
Round duct: D = 2 × √(144 / π) ≈ 13.5" → use 14" round (velocity ≈ 748 FPM)
Equivalent rectangular: 16" × 10" (De ≈ 13.7", velocity ≈ 720 FPM)
Use 14" round or 16" × 10" rectangular (both inside 700-900 FPM)