Superheat & Subcooling Calculator

Diagnose refrigerant charge in seconds. Calculate superheat and subcooling for R-410A, R-454B, R-22, R-32, and R-407C systems with PT chart saturation lookup and instant charge interpretation.

Use Calculator in App

What is Superheat & Subcooling?

Superheat is the number of degrees the refrigerant vapor is heated above its saturation (boiling) temperature at a given pressure. Subcooling is the number of degrees the liquid refrigerant is cooled below its saturation (condensing) temperature. Together they are the two most important measurements for diagnosing refrigerant charge and system performance.

Superheat protects the compressor by confirming that only vapor — never liquid — returns to it, while subcooling confirms the condenser is fully condensing refrigerant into liquid before it reaches the metering device. On a properly charged TXV system, technicians target 8-14°F of superheat and 10-18°F of subcooling.

Superheat & Subcooling Formulas

Superheat Formula

Superheat = Suction Line Temp − Evaporator Saturation Temp

Measure suction line temperature near the outdoor unit and look up the evaporator saturation temperature on a PT chart using the measured suction (low-side) pressure. Target range on TXV systems: 8-14°F.

Subcooling Formula

Subcooling = Condenser Saturation Temp − Liquid Line Temp

Look up the condenser saturation temperature on a PT chart using the measured liquid/high-side pressure, then subtract the liquid line temperature measured at the condenser. Target range: 10-18°F (verify against the equipment charging label).

Charge Diagnosis: Target Ranges & Interpretation

Superheat and subcooling only mean something when you compare them to their target ranges. Read the two numbers together to pinpoint what a system is actually doing:

  • Target superheat (TXV systems): 8-14°F. Fixed-orifice systems use the manufacturer's charging chart instead.
  • Target subcooling: 10-18°F — confirm the exact value on the equipment's charging label.
  • High superheat + low subcooling: undercharged or a refrigerant leak — find and repair the leak before adding refrigerant.
  • Low superheat + high subcooling: overcharged — recover refrigerant.
  • High superheat + high subcooling: a restriction in the liquid line or metering device (starved evaporator with refrigerant backing up in the condenser).
  • Low superheat (below 5°F): flooding risk — liquid refrigerant is returning to the compressor and can cause valve or bearing damage.

Always confirm charge against the manufacturer's charging chart and current operating conditions — outdoor dry bulb, indoor wet bulb, and airflow all shift the target numbers.

PT Chart Reference (Saturation Temperatures)

Saturation TempR-410A (psig)R-22 (psig)R-454B (psig)
32°F1015899
40°F11869116
45°F13076128
95°F290182285
110°F365226358
120°F418260410

Approximate saturation pressures for quick field reference. The 32-45°F rows are typical evaporator (low-side) conditions; the 95-120°F rows are typical condenser (high-side) conditions. R-454B and R-407C are zeotropic blends with temperature glide — use dew point for superheat and bubble point for subcooling. These values are estimates; always confirm against the manufacturer's PT chart or a digital PT tool before charging.

Superheat & Subcooling Calculation Example

Problem:

An R-410A split system with a TXV reads 105 psig suction pressure with a 60°F suction line temperature, and 330 psig liquid pressure with a 96°F liquid line temperature. Find the superheat and subcooling and diagnose the charge.

Solution:

Evaporator saturation temp at 105 psig ≈ 34°F

Superheat = 60°F − 34°F

Superheat = 26°F (above the 20°F starved threshold)

Condenser saturation temp at 330 psig ≈ 101°F

Subcooling = 101°F − 96°F

Subcooling = 5°F (at the low-charge threshold)

High superheat combined with low subcooling points to an undercharged system or refrigerant leak. Find and repair the leak before adding refrigerant, then verify against the manufacturer's charging chart for the current operating conditions.

Skip the Math - Use Ventora

Get instant superheat and subcooling calculations on your phone. Pick your refrigerant, enter your pressures and line temperatures, and get results in seconds — with saturation lookup and a plain-language charge diagnosis.

Download Free on App Store

Get All Calculators in One App

Download Ventora for instant access to all HVAC calculators, AI assistant, HVAC code reference, and more. Free to try.

Download on App Store