Refrigerant Charge Calculator
Dial in the correct charge on fixed-orifice systems using the target superheat method, verify compression ratio, and compare today's refrigerants — R-410A, R-454B, R-32, R-22, and R-407C.
Use Calculator in AppWhat is Target Superheat Charging?
Target superheat charging is the method used to set the correct refrigerant charge on fixed-orifice systems (piston or cap-tube metering). Because a fixed orifice does not modulate like a TXV, the superheat you should see changes with the indoor wet bulb and outdoor dry bulb. You calculate that target, measure the actual superheat, and adjust the charge until the two match.
High superheat means the evaporator is starved — the system is undercharged, so add refrigerant. Low superheat means liquid is flooding back — the system is overcharged, so recover refrigerant. Systems with a TXV hold superheat nearly constant and are charged to subcooling instead.
Target Superheat Chart (Fixed Orifice)
Carrier method: Target SH = (3 × Indoor Wet Bulb − 80 − Outdoor Dry Bulb) ÷ 2. Read the target superheat (°F) at the intersection of the measured indoor wet bulb and outdoor dry bulb.
| Indoor WB \ Outdoor DB | 75°F | 85°F | 95°F | 105°F |
|---|---|---|---|---|
| 62°F | 16° | 11° | 6° | 1° |
| 64°F | 19° | 14° | 9° | 4° |
| 66°F | 22° | 17° | 12° | 7° |
| 68°F | 25° | 20° | 15° | 10° |
| 70°F | 28° | 23° | 18° | 13° |
*Values are rounded approximations of the Carrier fixed-orifice method for reference only. Always charge to the manufacturer's charging chart on the unit's data plate. The superheat method applies to fixed-orifice systems in cooling mode only — TXV systems are charged by subcooling.
Refrigerant Comparison Chart
Global warming potential (GWP), ASHRAE 34 safety class, and phase-down status for the refrigerants you'll see most in the field. Under the AIM Act, new residential and light-commercial equipment must use refrigerants with GWP under 700 as of Jan 1, 2025.
| Refrigerant | Type | GWP | Safety Class | Status | Typical Use |
|---|---|---|---|---|---|
| R-22 | HCFC | 1,810 | A1 | Phased out (2020 ban) | Legacy AC; service on reclaimed supply only |
| R-410A | HFC blend | 2,088 | A1 | Phasing down (2025 equip. ban) | Outgoing standard for residential AC/heat pumps |
| R-454B | HFC/HFO blend | 466 | A2L | New standard (2025) | Designated R-410A replacement; similar pressures |
| R-32 | HFC | 675 | A2L | Active, growing | Mini-splits and global markets (Daikin, LG) |
| R-407C | HFC blend | 1,774 | A1 | Active (commercial) | Commercial AC and some R-22 retrofits |
A2L refrigerants are mildly flammable and require leak detection, ventilation, and A2L-rated installation practices per ASHRAE 15/34.
Compression Ratio & Typical Operating Pressures
Compression ratio compares absolute discharge to absolute suction pressure: CR = (Discharge psig + 14.7) ÷ (Suction psig + 14.7). A healthy residential system in cooling runs about 2.5:1 to 3.5:1. A high ratio (dirty condenser, overcharge, non-condensables, or low suction from a restriction or undercharge) drives up discharge temperature and shortens compressor life.
Charging Example
Problem:
A fixed-orifice R-410A split system reads 64°F indoor wet bulb and 90°F outdoor dry bulb. Measured superheat is 18°F, suction is 118 psig, and discharge is 400 psig. Is the charge correct?
Solution:
Target SH = (3 × 64 − 80 − 90) ÷ 2 = (192 − 170) ÷ 2 = 11°F
Measured 18°F is above the 11°F target → superheat is high → the system is undercharged.
Compression ratio = (400 + 14.7) ÷ (118 + 14.7) = 414.7 ÷ 132.7 = 3.1:1 (healthy range).
Add R-410A slowly until superheat drops to ~11°F, then re-verify.
Instant Refrigerant Charging with Ventora
Enter your wet bulb, dry bulb, and gauge readings — get target superheat, live compression ratio, and add/remove-charge guidance instantly. Built-in PT charts for R-410A, R-454B, R-32, R-22, and R-407C.
Download Free on App Store